Plan Submittal Requirements
- Floor plans showing the location of the gas detection system in the building that is fully dimensioned and to scale 
- All details on system components and building construction features shall be clearly legible. 
- Identify the type of gas detection system or equipment being installed or modified: - Type of gas being detected 
- Gas alarm threshold limits 
- Sensor locations 
- Alarm notification appliances 
 
- Submit Safety Data Sheets (SDS) for all gases being detected. 
- Plans on any interlock systems (safety features) as required. 
- Adequate, concise, and sufficient information as required by MSFC and NFPA shall be clearly indicated on the plans. 
- Manufacturer’s data sheets shall be provided for all equipment. 
- Designers name, business name, contact information, and proof of licensure (if required). 